Re: Women's only multi-accommodation restrooms on upper level

Jim Fruit ·
The only available guidance is in section 213. It would appear that the men's room one floor removed is ok.
Reply

Re: Women's only multi-accommodation restrooms on upper level

M. Handler,Architect ·
Yes it is Okay as long as the fixture count is met. 422.4.1 Access to Toilet Facilities. In multi-story building accessibility to the required toilet facilities shan not exceed one vertical story . Access to the required toilet facilities for customers shall not pass through areas designated as for employee use only such as kitchens, food preparation areas, storage rooms, closets, or similar spaces. Toilet facilities accessible only to private offices shall not be counted to determine...
Topic

Women's only multi-accommodation restrooms on upper level

Rod Alonzo_modesto ·
I am working on a major remodel of an existing retail facility (single story with mezzanine and elevator)  that is being converted to a fitness facility. As part of the remodel we are keeping some existing accessible multi-accommodation...
×
×
×
×
×